AWG describes a logarithmic series of conductor sizes. Square millimetres (mm²) describe cross-sectional area directly. A conversion connects the geometry; it does not establish that two cable products meet the same requirements.
Open the AWG to mm² converter to compare values while reading.
AWG to mm² chart for common sizes
These are geometric conductor values, rounded to three decimal places. The diameter is a solid circular equivalent. Neither column includes insulation or sheath.
| AWG | Area (mm²) | Equivalent diameter (mm) |
|---|---|---|
| 4/0 | 107.219 | 11.684 |
| 3/0 | 85.029 | 10.405 |
| 2/0 | 67.431 | 9.266 |
| 1/0 | 53.475 | 8.251 |
| 1 | 42.408 | 7.348 |
| 2 | 33.631 | 6.544 |
| 4 | 21.151 | 5.189 |
| 6 | 13.302 | 4.115 |
| 8 | 8.366 | 3.264 |
| 10 | 5.261 | 2.588 |
| 12 | 3.309 | 2.053 |
| 14 | 2.081 | 1.628 |
| 16 | 1.309 | 1.291 |
| 18 | 0.823 | 1.024 |
| 20 | 0.518 | 0.812 |
Use the interactive converter for the full gauge range, reverse conversion and sizes between table entries. Do not round an input to the table before doing a calculation.
Why a smaller AWG number means a bigger wire
The AWG sequence increases conductor diameter as the gauge number falls. Its geometric definition uses 0.005 inches at 36 AWG and 0.46 inches at 4/0 AWG. In millimetres, the diameter formula is:
d = 0.127 × 92^((36 − n) / 39)
The area is π × d² / 4. For 1/0 use n = 0; for 2/0, 3/0 and 4/0 use −1, −2 and −3.
Example: 10 AWG and 6 mm²
10 AWG has a calculated area of approximately 5.261 mm². A nominal 6 mm² conductor is larger by about 14% when comparing those area numbers. It is not an exact conversion.
For 12 AWG the calculated area is approximately 3.309 mm². A commonly listed nominal metric size above this value is 4 mm², but calling the two sizes equivalent hides a meaningful difference.
Nearest is different from at least
When converting 6 mm² back to AWG, the nearest gauge by the continuous gauge formula is 9 AWG, approximately 6.634 mm². For another metric input, the nearest gauge may have less area than requested. Our converter reports the nearest result and a separate gauge with at least the entered area.
Neither result is a recommendation to install that wire. Gauge availability also varies by supplier and product.
Area is not outside diameter
Conductor area excludes insulation and sheath. For stranded conductors, the equivalent solid diameter does not describe the physical bundle diameter because strands leave gaps and may be compacted. Insulated cable outside diameter must come from the manufacturer’s datasheet.
What conversion cannot tell you
A matching area does not settle ampacity, voltage rating, flexibility, temperature rating, terminal compatibility or local compliance. Those questions require the actual cable construction and installation conditions.
For a copper material estimate, use the converted area in the copper weight calculator.
Reference and method
Compare calculated values with Multi/Cable’s AWG cross-reference. Rounded reference values can differ slightly from an unrounded formula result. Our methodology explains the distinction between geometric estimates and installation design.
Comparing supplier specifications
Keep the original size designation when requesting a quote. For example, ask for “10 AWG copper conductor” if that is the specified product, rather than silently changing the request to “6 mm².” If you also provide a conversion, label it as an approximate geometric area.
Compare conductor material, stranding, conductor resistance, voltage rating, insulation and approvals as separate fields. A size-conversion chart cannot confirm those properties. Our 10 AWG versus 6 mm² comparison shows the area, diameter and theoretical copper-weight differences for that frequently compared pair.
Frequently asked questions
Is 4/0 AWG the same as 0000 AWG?
They identify the same position in the AWG sequence. For the formula above, use n = −3, giving approximately 107.219 mm². It is not a nominal 120 mm² conductor.
Can cable outside diameter be converted directly into mm²?
Not into conductor area without construction information. Outside diameter includes layers and spaces that do not represent conductor metal. Even a bare stranded bundle needs strand geometry or a manufacturer specification; using its envelope as a solid metal circle can overstate metal area.