AWG to mm² converter

Convert wire gauge and conductor area. Compare sizes using the reference table.

AWG ⇄ mm²

Inputs

Lower AWG numbers represent larger conductors.

Result

Cross-sectional area
5.261 mm²

Area comparison only; not an installation recommendation.

Formula

d = 0.127 × 92(36 − n) / 39
A = π × d² / 4

Scope & assumptions

Geometry only. Ampacity depends on cable construction, insulation, installation, temperature, grouping and local rules. Diameter is a solid-conductor equivalent, not cable outside diameter. Nearest sizes are not necessarily interchangeable.

Worked example

10 AWG is approximately 5.261 mm², with a solid-equivalent diameter of 2.588 mm. A nominal 6 mm² conductor is larger in area; it is not an exact equivalent.