To estimate conductor copper mass, multiply total copper cross-sectional area by conductor length and material density. Keep units consistent and distinguish conductor mass from total cable weight.
Use the copper wire weight calculator for metres, kilometres or feet.
The practical formula
Copper weight (kg) = cores × area per core (mm²) × length (m) × density (g/cm³) ÷ 1,000
One square millimetre extending for one metre is one cubic centimetre. Multiplying by density gives grams; divide by 1,000 for kilograms.
Example: three 2.5 mm² cores, 100 metres
At an assumed density of 8.96 g/cm³:
3 × 2.5 × 100 × 8.96 ÷ 1,000 = 6.72 kg
For one kilometre of the same nominal construction, the result is 67.2 kg of theoretical conductor copper. The mass of the finished cable will be higher because other components are excluded.
Copper weight per metre and per kilometre
At the default density, a single conductor has 0.00896 × area kilograms of theoretical copper per metre. Multiply by core count only once.
| Area per conductor | One conductor, kg/m | Three equal cores, kg/m | Three equal cores, kg/km |
|---|---|---|---|
| 1.5 mm² | 0.01344 | 0.04032 | 40.32 |
| 2.5 mm² | 0.02240 | 0.06720 | 67.20 |
| 4 mm² | 0.03584 | 0.10752 | 107.52 |
| 6 mm² | 0.05376 | 0.16128 | 161.28 |
| 10 mm² | 0.08960 | 0.26880 | 268.80 |
| 16 mm² | 0.14336 | 0.43008 | 430.08 |
These are calculated conductor quantities, not product datasheet weights. For a four-core construction or an unequal protective conductor, see the 3-core and 4-core examples.
Length units: metres, kilometres and feet
Use 1 km = 1,000 m and 1 ft = 0.3048 m. For 1,000 feet of three 2.5 mm² conductors, the cable length is 304.8 metres:
3 × 2.5 × 304.8 × 8.96 ÷ 1,000 = 20.48256 kg
The calculator’s unit selector converts cable length before calculating mass. Do not convert feet yourself and then leave the selector set to feet; that applies the conversion twice.
Choose an appropriate density
Our default, 8.96 g/cm³, is the pure copper value listed in NIST’s material composition data. Actual electrical conductor specifications may use another density. The calculator makes density editable rather than silently presenting one value as universal.
For example, using 8.89 instead gives 6.6675 kg in the same example. Use the density specified for your material when you have it.
Unequal cores and additional copper
For three 16 mm² cores plus a 10 mm² copper protective conductor, calculate each group separately. At 100 m and 8.96 g/cm³, the groups are 43.008 kg and 8.96 kg, totalling 51.968 kg.
Screens, braid and drain wires require their own geometry. Do not simply add their outside diameter to conductor area.
Why an actual cable can differ
Nominal area is a designation and may not be the measured geometric area. Stranding adds conductor path length; compaction, tolerances and construction details also affect actual metal quantity. A nominal-area calculation is useful for comparison and planning, not for certifying compliance, scrap yield or invoice weight.
Turn weight into a material cost estimate
Divide kilograms by 1,000 and multiply by your price per metric tonne. Our copper cost calculator compares two prices. It excludes processing losses, premiums and every non-copper component.
What to use for ordering and freight
For a purchase-order metal adjustment, use the agreed conductor metal weight and contractual pricing basis. For freight, use finished-cable mass and reel or package tare weight. The copper weight versus finished cable weight guide explains why the figures answer different questions.
If a supplier provides kg/km, multiply by the ordered metres and divide by 1,000. Confirm whether that kg/km figure describes conductor copper, all metallic components or the complete cable before comparing it with a calculated result.